GB - 24CP-Parameterdulation is switched off!CP.29 Analog output 1 / FunctionCP.29 defines the function of analog output 1.Value Function Scaling factor0…100 % (0…±100 %)0 Absolute actual frequency CP.3 0…100 Hz1 absolute set frequency CP.2 0…100 Hz2 actual frequency CP.3 0…±100 Hz3 set frequency CP. 2 0…±100 Hz4 output voltage CP.9 0…500 V5 DC link voltage CP.7 0…1000 V6 apparent current CP.4 0…2 • rated current7 active current ru.17 0…2 • ±rated current8…10 only application mode11 absolute active current ru.17 0…2 • rated current12 power stage temperature ru.38 0…100 °C13 motor temperature ru.46 0…100 °C14…18 only application mode19 ramp output frequency ru.2 0…±100 Hz20 absolute ramp output frequency ru.2 0…100 HzCP.31 Relay output 1 / function (terminals X2A.24...26)CP.32 Relay output 2 / function (terminals X2A.27...29)The switching level of CP.31 is pre-set to 100,00.The switching level of CP.32 is adjusted by CP.33!Va-lueFunction0 No function (generally off)1 Generally on2 Run signal; also by DC-braking3 Ready signal (no error)4 Fault relay5 Fault relay (without auto-reset)6 Warning or error message at abnormal stopping7 Overload pre-warning8 Overtemperature alert signal power stage9 External Overtemperature alert signal motor11 Overtemperature alert signal interior OHI12 Cable breakage 4...20 mA on analog input 114 max. constant current (Stall, CP.25) exceeded15 max. ramp current (LA-Stop, CP.24) exceeded16 DC-braking active20 Actual value = set value (CP.3 = Fcon; rcon; not at noP, LS, error, SSF)21 Accelerate (CP.3=FAcc, rAcc, LAS)22 Decelerate (CP.3 = FdEc, rdEc, LdS)23 Real direction of rotation = set direction of rotation24 Utilization (CP.6) > switching level