Contents - contact information
- safety information
- battery safety
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Introduction
- How an Inverter/Charger Works
- Features and Benefi ts
- Figure 1-2, Electrical Connection Points
- Figure 1-3, Left Side Features (MS2012, MS2812, MS2024, MS4024, MS4048)
- Figure 1-4, Left Side Features (MS2000 Series)
- Installation
- Figure 2-1, Simplifi ed Installation for Permanent Installations (MS Series)
- Figure 2-2, Simplifi ed Installation for Permanent Installations (MS2000)
- Locating the Inverter
- Mounting the Inverter
- Figure 2-4, MS Dimensions (MS2012, MS2812, MS2024, MS4024, MS4048)
- Figure 2-5, MS Dimensions (MS2000)
- Wiring the Inverter – General Requirements
- DC Wiring
- Figure 2-6, DC and Battery Temperature Sensor Wiring
- DC Wire Sizing
- DC Cable Connections
- Wiring the Battery Bank
- Battery Temperature Sensor Installation and Wiring
- Wiring the Inverter to the Battery Bank
- AC Wiring
- Recommended GFCI (Ground Fault Circuit Interruption) Outlets
- AC Conductor Wiring (MS2012, MS2812, MS2024, MS4024, & MS4048)
- AC Wiring Confi gurations (MS2012, MS2812, MS2024, MS4024, & MS4048)
- Figure 2-11, AC Wiring for Single In – Single Out (30 A) Confi gurations
- Figure 2-12, AC Wiring for Single In – Single Out (60 A) Confi gurations
- Figure 2-13, AC Wiring for Single In – Dual Out Confi gurations
- Figure 2-14, AC Wiring for Dual In – Single Out Confi gurations
- Figure 2-15, AC Wiring for Dual In – Dual Out Confi gurations
- AC Conductor Wiring (MS2000 models)
- AC Wiring Confi guration (MS2000 models)
- Figure 2-16, AC Wiring for MS2000 Models
- Figure 2-17, AC Wiring for MS2000-15B/-20B Models
- Grounding Inverters
- Sizing the Grounding Electrode Conductors
- Figure 2-20, Multiple Connections to DC Ground Rod (Method 2)
- System Bonding Jumper
- Grounding on Boats
- Neutral to Safety Ground Bonding
- Disabling the Neutral-to-Ground Connection
- Inverter Notifi cation Requirements
- Functional Test
- Figure 2-27, AC Voltage Checks
- Operation
- Figure 3-2, Power Flow – Inverter Mode (MS2000 models)
- Standby Mode
- Battery Charging
- Figure 3-7, Automatic 4-Stage Charging Graph
- Transfer Time
- Protection Circuitry Operation
- Inverter Startup
- Factory Default Values
- Inverter Fan Operation
- Maintenance and Troubleshooting
- Troubleshooting
- Resetting the Inverter
- Appendix A – Specifi cations and Optional Equipment
- A-2 Inverter Effi ciency
- A-4 Temperature and Inverter Output
- A-6 Optional Equipment and Accessories
- Appendix B – Battery Information
- B-5 Battery Bank Sizing Worksheet
- B-6 Battery Wiring Confi gurations
- Figure B-4, Battery Bank Wiring Examples (12-volt)
- Figure B-5, Battery Bank Wiring Examples (24-volt)
- Figure B-6, Battery Bank Wiring Examples (48-volt)
- Appendix C – Power Consumption & Output Waveforms
- Appendix D – Inverter/Charger Terminology
- Appendix E – Warranty & Service
|
© 2016 Sensata TechnologiesPage 19Installation2.4.4 Wiring the Battery BankWARNING: Lethal currents will be present if the positive and negative cables attachedto the battery bank touch each other. During the installation and wiring process, ensurethe cable ends are insulated or covered to prevent touching/shorting the cables.Info: DO NOT connect the DC wires from the battery bank to the inverter until 1) all DCand AC wiring is complete, 2) the correct DC and AC overcurrent protection has beeninstalled, and 3) the correct DC voltage and polarity have been verified.Info: For the MS Series inverter/charger to perform optimally, a minimum battery bankof 200 AH is recommended for moderate loads (<1000W) and greater than 400 AH forheavy loads (≥1000W).Depending upon the voltage of the batteries you use in the installation (6 or 12 VDC), the batteriesmust be wired in series, parallel, or series-parallel to provide the correct voltage (see AppendixB – Battery Information for guidance on wiring batteries together). The interconnecting DC wiresmust be sized and rated exactly the same as those used between the battery bank and the inverter.Place the batteries as close as practical to the inverter, preferably in an insulated and ventilatedenclosure. Allow adequate space above the batteries to access the terminals and vent caps (asapplicable). Also, allow at least 1” (2.5 cm) of space between the batteries to provide good airflow. DO NOT mount the batteries directly under the inverter.CAUTION: Install batteries in a well ventilated area. Batteries can produce explosivegasses. For compartment or enclosure installations, always vent batteries to the outside.Info: To ensure the best performance from your inverter system, batteries should beof the same size, type, rating, and age. Do not use old or untested batteries.Figure 2-7, Battery HardwareInstallationFigure 2-8, Inverter DC HardwareInstallationbattery cable(with ring lug)nutsplit washerBatteryTemperatureSensorbatterypostCAUTION:Ensure nothing isplaced betweenthe cable ring lugand battery post.5/16-18Flange orKep nutbattery cable(with ring lug)Inverter DC terminal( 5/16–18 bolt,5/8" usable length )CAUTION:Ensure nothing isplaced between the DCterminal and ring lug.
PreviousNext |