06 iVECTOR Specification Data3.1 Unit SizesAll iVECTORs are the same height and depth and there is achoice of 5 different lengths as detailed in the table (right). Theperformance data for each model is supplied in the followingsections of this guide.Model Nominal Height(mm)Depth(mm)Length(mm)iV60x080 600 153 800iV60x100 600 153 1000iV60x120 600 153 1200iV60x140 600 153 1400iV60x160 600 153 16003.2 OutputsThe heat output of the iVECTOR is affected by the flow rate ofwater through its heat exchanger, even when the mean watertemperature is constant. Each iVECTOR model requires thespecified flow rate to ensure the temperature drop will bereasonable, as shown in the outputs table. For quietestoperation MYSON recommends sizing the iVECTOR based onnormal fan speed.Model Flow(l/h) ΔT20 ΔT25 ΔT30 ΔT35 ΔT40 ΔT45 ΔT50Mean water - air temp difference (watts)iV60x080iV60x100iV60x120iV60x140iV60x160Fan SpeedNormal 341 738 940 1146 1355 1567 1781 1997Medium 341 989 1260 1537 1817 2101 2388 2678Boost 341 1360 1733 2113 2499 2889 3284 3682Normal 450 1012 1289 1572 1859 2149 2443 2739Medium 450 1352 1723 2101 2484 2872 3265 3661Boost 450 1892 2412 2941 3477 4020 4569 5124Normal 600 1214 1548 1887 2231 2580 2932 3288Medium 600 1643 2094 2553 3018 3490 3967 4448Boost 600 2409 3070 3743 4425 5117 5815 6521Normal 700 1428 1820 2219 2624 3034 3449 3867Medium 700 1945 2478 3022 3573 4131 4695 5265Boost 700 2916 3716 4531 5357 6194 7040 7894Normal 800 1647 2099 2560 3027 3499 3977 4460Medium 800 2246 2863 3491 4127 4772 5424 6082Boost 800 3422 4362 5318 6288 7270 8263 9266ModelCooling (watts )Condition 7-12-27Total SensibleNormal 707 527Medium 1126 829Boost 1648 1227Normal 1011 753Medium 1600 1178Boost 2304 1716Normal 1250 931Medium 1960 1442Boost 2918 2173Normal 1490 1110Medium 2320 1707Boost 3533 2631Normal 1729 1288Medium 2679 1972Boost 4147 3088iV60x080iV60x100iV60x120iV60x140iV60x160Fan SpeedRelative Humidity: Sensible cooling at 50%.