L NAPCO Security Systems X GEM-X255 Installation InstructionsWI1093C 3/04 !Page 9SUMMARY OF UL REQUIREMENTSResidential! Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.! Initiating loops supervised if longer than 3 feet! FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)! Minimum alarm timeout of 5 minutes! Maximum exit time: 60 seconds! Maximum entry time: 45 seconds! Do not program ìSwinger Shutdownî, ìAuto Armingî, ìSelective Bypassî, ìInterior (Group) Bypassî, or ì50 msor 20ms Loop Responseî! ìAbort Delayî may not exceed 45 seconds! Program ìDisable Callback Downloadî! Automatic dialer may not dial a police station number that has not been dedicated for such service! System must be tested at least weekly under AC/battery and Battery-Only conditions! Replace the rechargeable battery at least every 5 years! If the battery is heavily discharged, replace it or have it tested by a qualified technician! For silent panic, connect only to UL-listed holdup devices! All zones must be programmed for ìPriorityî! Do not program any zones for ìKeyswitch Armingî! System must be serviced at least once every year! Residential Fire and Combination Residential Fire & Burglary must program ìResidential Fireî! Keypad Expansion (EZM) Zones are not to be used as fire zonesCompatible Smoke Detectors2 Wire Smoke DetectorsManufacturer Model BaseNAPCO FW-2 N/ASentrol/ESL 711U, 712U, 701U, 702U,721U, 721UT, 702RE, 702RU722U, 731U, 732USystem Sensor 1100, 1151, N/A1400, 2100, N/A2100T, 2100S, N/A2100TS, 2151, N/A2400, 2400TH N/ANote: Voltage Rating: 8.5ñ13.3 VDCMaximum Number of Detectors: 104 Wire Smoke DetectorsManufacturer Model BaseGentex 812, 812T, 812P, N/A812PT, 812PH, N/A8120, 8120T, N/A8120P, N/A8120PTY, 8120-PH N/AHochiki SLG-12 w/YBC-RL4-RA base N/ANAPCO FW-4 N/ASentrol/ESL 445AT, 445C, N/A445CT, 445CR, N/A445CRT N/ASystem Sensor 1112, 2112, N/A21112T, 211TSRB N/A1412TH, 2412TH N/A2312/24T, 1412, N/ANote: Subtract total smoke-detector alarm currentfrom available standby current.UL Compatible Smoke Detectors (Providing UL Recognition or Listing)Note: Any normally-open devices that do not require power from the control panel may be used (such aspull stations, waterflow and thermostats), if acceptable to the authority having jurisdiction.