FlexPAK 800/1000EN204 PLC settingsThe following PLC displays show the different settings that can be configured for the unit.4.1 Find a parameter and set its valueESC OKThu 10:452018-02-01ESC OKStop >Program >Setup >Network >Diagnostics >ESC OKSet ParameterProgram NameESC OKFlexPakHi Vacuum UnitOFFTime To Service2000 hoursESC OKH-Meter 1/1MI =2000h:0mOT =0h:15mMN =1999h:45MN Ext =2000ESC OKH-Meter >SSR_Time >Cool_Tmr >ClenCyl >FItClean >DIRTime ZDo the following to find a parameter and set its value:1. From the PLC status screen, press the down arrow to go to the date and timescreen.2. Press ‘Escape’ ESC to go to the main menu.3. Press the down arrow to go to ‘Program’. Press ‘OK’ OK to confirm.4. Select ‘Set Parameter’. Press ‘OK’ OK to confirm.5. Use the up or down arrows to find the parameter. Press ‘OK’ OK to confirm.6. Use the left and right arrows to select a value.7. Use the up or down arrows to set the value. Press ‘OK’ OK to confirm.8. Press ‘Escape’ ESC to go to the main menu.9. Press ‘Escape’ ESC to go to go to the date and time screen.10. Press the up arrow to exit.NOTE! There are several other input menus on the same level as the date and time screen.If pressing the down arrow takes the PLC to one of those menus, use the left arrowto get to the date and time screen.NOTE! The blinking cursor shows the current value that can be changed.