Refrigerator Service Manual / Manuel d'entretien du réfrigérateur / Manual de servicio del refrigerador463163 Models / Modèles 3163 / Modelos 3163Burner Ignites But Flame Will Not HoldNONOYESYESYES YES YES YES YESYES YES YES YESRemove jumper and reconnect white wires. Check for voltage at terminalsof interrupter. (Refer to Figure 19 for correct method of measuringmilli-volts)NOAdjust main gaspressure to 11"W.C.NONONONONONONONOIs the DC voltageat terminal blockbetween 10.5 -15.4 VDC?Is the main gassupply on? Is refrigerator’smanual shut-offvalve on?Is vent terminalhousing freefromobstructions?Is gas supplypressure at10.5" - 11" W.C.?Set thermostatto maximumsetting.Correct DCvoltage input. Turn main gassupply on. Turn manualshut-off valveon.Clear vent terminalof obstruction.Remove whitewires and jumpinterrupterterminals.Are white wiresfrom relighter tointerruptersecure & tight?Is interrupterconnection atsafety valvetight?Is thermocoupleconnection at theinterrupter tight?Is tip of thethermocouple inflame and cleanof carbon?Is gas pressure atpressure tap teebetween 10.5 - 11"W.C.?Does flamehold? Secure wireconnections. Tightenconnection. Tightenconnection.Reposition or cleanthermocouple. Replacethermostat.Replacerelighter.0 milli-volts onboth terminals. 10-15 milli-volts onboth terminals. 16-30 milli-volts onone terminal, 0milli-volts on theother.16-30 milli-voltson bothterminals.Replacethermocouple. Replace safetyvalve.Replace safetyvalve.Replaceinterrupter.Note : If the negative DC supply connection is lost, the flame indicator light will remain on all the time, even without the flame present.NOTest D, cont’d - Burner Ignites But Flame DiminishesTroubleshooting, cont’d.Fig. 20 - Gas Circuit Burner Test