Configuring and Modifying Temperature, Pump and Melter Settings 6-3Part 1120130 2011 Nordson CorporationManage Temperature SettingsThe following table details each temperature settings.Button Use this to… Default RangeSetpoints Define the setpoint temperatures for heated(internal and external) zones.Touch to define one global temperaturefor all connected zonesTouch (the default) to define each zoneindividually.NOTE: To minimize charring the adhesivematerial, you can define the hopper setpointtemperature up to 15C (30F) cooler than thereservoir setpoint temperatureNOTE: The Hopper setpoint temperaturecannot exceed that of the reservoir.Internal Zones:Temp: 175C(350F)External Zones:Temp: 175C(350F)Min: 40C (100F)Max: 230C(450F)TemperatureLimitsTemperature LimitsDefine the over and under temperaturethreshold values, allowing the system toalert you before an over/under temperaturefault occurs.NOTE: For setpoint limits, the system usesthe differential temperature conversionmethod. For Celsius to Fahrenheit multiplyCelsius by 1.8. For Fahrenheit to Celsiusdivide by 1.8Over Temp Limit:15C (25F)Over TempLimit:Min: 5C (10F)Max: 60C(110F)Under Temp Limit:25C (50F)Under TempLimit:5C (10F)60C (110F)PID Settings Define the Proportional, Integral andDifferential (control aspects) of standard orlarge applicators, hoses and air heaters.Zone A – HoseZone B – StandardApplicatorHose StandardApplicatorLargeApplicator AirheaterHeater ZoneControlEnable or Disable individual external zones. Internal : EnabledExternal: DisabledNOTE: If youdefined a Globaltemperature, thenall external zoneswith connecteddevicesautomaticallybecome Enabled.EnabledDisabledReady Delay Define the amount of time to delay theMelter “Ready” (green) status, therebyallowing enough time for the hot meltmaterial in the reservoir to reach its normaloperation.0 minutes(disabled)Min: 0 minutesMax: 1440minutes