Read Status Options 4. Read StatusAFP-300/AFP-400 Operations PN 50260:C1 05/22/97 17Table 13 contains descriptions of the fields shown in Figure 12:Table 13 Default Read Status Values for a DetectorRead Status for a Zone AddressNote: Press L to read apoint or zone with next highestaddress; or press M to reada point or zone with next lowestaddress.From the Read Point screen, press z, then enter the zone address (01-99) Figure 13shows the default Read Status display for a zone:Figure 13 Read Status Display for a Zone AddressField DescriptionSMOKE (PHOTO) Type code of the detector.DETECTOR ADDR 101 Default custom label: 101 (1=loop 1; 01=address 01).Z03 Default zone selection:Zone 01 (Heat detectors)Zone 02 (Ion detectors)Zone 03 (Photo detectors)Zone 04 (Laser detectors)Zone 05 (Multi detectors)You can change zones as well as add four more zones for eachdetector’s CBE.AL:5 The Alarm sensitivity level, with 9 the least sensitive Alarmlevel and 1 the most sensitive Alarm level.PA:0 Shows the Pre-Alarm level setting—a number between 0 and9—as follows:0 – no Pre-Alarm.1 – most sensitive Pre-Alarm level.9 – least sensitive Pre-Alarm level.*V * The asterisk (*) indicates the cooperative multidetector mode:A combines the detector's alarm decision with the next addressabove.B combines the detector's alarm decision with the next addressbelow.C combines the detector's alarm decision with the next addressabove and the next address below.V – indicates Alarm Verification (V=on, *=off).OFF SOFTWARE ZONE FLOOR 5 MAIN BLDGZ04Zone status (ON or OFF)Zone numberTechnical Manuals Online! - http://www.tech-man.com