AFP-3030 Installation Manual — P/N DOC-01-031:F 19/11/2018 23Wiring a Signalling Line Circuit (SLC) InstallationPRN Printer SettingsSet the printer options (under the menu area) according to the settings listed in Table 3.3.3.9 Wiring a Signalling Line Circuit (SLC)3.9.1 SLC OverviewCommunication between the CPU and intelligent and addressable initiating, monitor, and control devices takes place through a Signal-ling Line Circuit (SLC). This manual provides requirements and performance details specific to this control panel; for installation infor-mation and general information, refer to the SLC Wiring Manual.For electrical specifications, see Appendix A.2 “SLC Loops”. For additional notes on SLC resistance values, see Section 4.1 “Opera-tional Checks”.3.9.2 SLC CapacityThe AFP-3030 supports up to five pairs of LCM-320 and LEM-320 modules, providing from one to ten SLC loops. Loop capacitydepends on operating mode:• Flash Scan: 01-159 intelligent detectors, 01-159 monitor and control modules• CLIP: 01-99 intelligent detectors, 01-99 monitor and control modulesFlashScan devices can operate in either FlashScan or CLIP mode. Older models of CLIP devices only support addresses up to address99. CLIP loops are limited to 99 detectors and 99 modules.The following configuration guidelines may be used to improve the response times of CLIP loops:1. All manual pull stations must be assigned addresses from 1-20.2. Loops must be programmed for Rapid Poll (refer to the programming manual for specific instructions).3. Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module.*Protocol: When printing in graphics mode, set I/OSerial Protocol to “Robust XON/OFF”.Option SettingL/R Adjust 0Font HS DraftCPI 10 CPILPI 6 LPISkip 0.0ESC Character ESCEmulate FX-850Bidirectional Copy ONI/OInterfaceBufferSerialBaudFormatProtocol *Serial40K96008 Bit, None, 1 StopENQ/STXCG-TAB GraphicCharacter Set StandardCountry E-USA ASCIISelect Zero ONAuto-CR OFFAuto-LF OFFOption SettingMenu Lock ONLanguage EnglishPaperSingleForm AdjustTrac 1Form AdjustTrac 2Form AdjustAuto Sheet FeederForm Adjust12/7212/7212/7212/72Auto Tear OFFF-Eject OFFForm LengthTrac 1LinesStandardTrac 2LinesStandard6610.5”6610.5”Barcode OffBarmode UnsecuredOption SettingTable 3.3 PRN Setup OptionsNOTE: Response times for CLIP loops may vary. CLIP loops must be tested to assure that actuation of notificationappliances occurs within 10 seconds after activation of an initiating device.