Fire/Security Applications Section 4 ApplicationsNFS-3030 Installation PN 51330:C 10/28/2003 55Figure 40 Single Tenant Security System with Entry/Exit DelayProgramming Notes for Figure 40TENANT AArea6_b.cdrAREA 1(Perimeterand interior)To SignalingLine CircuitMMTo Central Station(via EIA-485 circuit)Entry/Exit DoorNFS-3030Central Station* Group Interface must bephysically located in eitherthe protected premises orthe Central StationKeyMotion DetectorContact SwitchContact Switch with MM ModulePull StationSmoke DetectorRKS-S Remote Key Switch with MM ModuleRemote AnnunciatorMM Security Access MonitorGroup Interface *CMMM CMNote: See “Programming Notes for Figure 40” and Figure 40.continued…1. Programming of Key Switch,Access Points, and Motion DetectionRKS Remote Key Switch with Monitor ModuleAddress: LXXMYYY (arbitrary)Type ID: ACCESS MONITORZone Map: (none)Custom Label: Arming SwitchContact Switches with Monitor ModulesAddress: LXXMYYY (arbitrary)Type ID: ACCESS MONITORZone Map: ZACustom Label: Exit Door #Motion Detectors with Monitor ModulesAddress: LXXMYYY (arbitrary)Type ID: ACCESS MONITORZone Map: ZBCustom Label: Motion Detection2. Programming of Logic EquationsLogic Equation for 1 minute exit delay:ZLa* = DEL(01:00, 00:00, address ofkey switch)Logic Equation for Trouble arming system:ZLb* = AND (ZA, address of keyswitch, NOT(Zla))Logic Equation to arm system:ZLc* = AND (ZLa, NOT(ZLb))Logic Equation providing 30-second entry delay:ZLd* = SDEL(00:30, 00:30, ZA)Logic Equation for Security Alarm:ZLe* = AND (ZLc, OR (ZLd))*Follow the following restrictions on values:a < b < c < d