The Main Menu General InformationNFS-3030 Operating P/N 51344:C 11/4/03 15Figure 1.5 Main Menu ScreenSoft KeysPressing the soft keys brings the user to the screens described below.1.7.1 Event Counts DisplayPressing the soft key to the left of the Event Counts Display message on the Main Menubrings up the Event Counts screen. This screen will automatically display if an off-normal eventrequiring acknowledgement occurs, unless the panel is in programming mode. Fire alarm eventswill display even in programming mode.Lines six and seven display current counts of off-normal events in six categories. The countsinclude both acknowledged and unacknowledged events.Figure 1.6 Events Count Display ScreenSoft KeysACKNOWLEDGE FIRE ALARM - Press this key to acknowledge an event. The command will readACKNOWLEDGE FIRE ALARM if the event is a fire alarm. It will read ACKNOWLEDGE if the eventis any other type. The command will not display if there are no events to acknowledge.MORE INFORMATION - Press this key to go to the MORE INFORMATION screen, described inSection 1.7.2 below. This button will not display if no off-normal events exist.L A K E V I E W G E N E R A L H O S P I T A LS Y S T E M N O R M A L1 1 : 5 8 : 4 5 A W E D J U N 2 5 , 2 0 0 3E V E N T C O U N T S D I S P L A Y R E A D S T A T U SP R O G R A M / A L T E R S T A T U SM U L T I P L E E V E N T L I S T P R I N T E R F U N C T I O N SH I S T O R Y D I S P L A Y B A C KF I R E A L A R ME L E V A T O R L O B B Y E A S T W I N GF I F T H F L O O R Z 0 0 5 S M O K E ( P H O T O )1 1 : 5 7 : 4 5 A W E D J U N 2 5 , 2 0 0 3 L 0 3 D 0 5 2E V E N T C O U N T SF I R E A L A R M S : 0 0 1 P R E A L A R M : 0 0 0 T R O U B L E : 0 0 0S U P E R V I S O R Y : 0 0 0 S E C U R I T Y : 0 0 0 D I S A B L E : 0 0 01 1 : 5 8 : 4 5 A W E D J U N 2 5 , 2 0 0 3A C K N O W L E D G E F I R E A L A R M S I G N A L S I L E N C EM O R E I N F O R M A T I O N S Y S T E M R E S E TP R O G R A M / A L T E R S T A T U S B A C KTechnical Manuals Online! - http://www.tech-man.com