Read Status Heat Detector40 NFS-3030 Operating P/N 51344:C 11/4/03The device is a detector (an input device) so by referring to the descriptions below, it can bedetermined that the point is in a normal state.Inputs: (detectors, monitor modules, zones)If the point is not in trouble or disabled, and the point is automatically controlled by the panel, thedisplay will be one of the following:AUTOMATIC INACTIVEAUTOMATIC ACTIVEAUTOMATIC PREALARMIf the point is disabled, the display will be one of the following. The Trouble Status field willappear if the point is in trouble.DISABLED INACTIVE <Trouble Status>*DISABLED ACTIVE <Trouble Status>*DISABLED PREALARM <Trouble Status>*If the point is in trouble, the display will read:TROUBLE INACTIVE <Trouble Status>*TROUBLE ACTIVE <Trouble Status>*TROUBLE PREALARM <Trouble Status>**The field <Trouble Status> will contain one of the device trouble messages listed in Table 2.1.Line 7 - The custom label for this point.Line 8 - Continuation of the point’s custom label, first zone, and device type.Lines 9,10 - a display of all the zones that contain the current point being read. These lines willhave values in them only if the device is a detector.Lines 11 through 14 - These lines display only if the device being read is a smoke or heat detector.Refer to the section More Information on page 16 for an explanation of these fields.Line 16 - B A C K - Press to return to the previous screen.3.3 Heat DetectorWhen a detector address is entered into the Point Select Screen and the ACCEPT soft key ispressed, the following screen will display if the detector is a heat detector.Figure 3.3 Heat Detector Screen - Read StatusDisplayLines 1 through 10 - Refer to the descriptions in "Smoke Detector" on page 39.Line 11 - VALUES - This field indicates the percentage of alarm value being read by the detector.L A K E V I E W G E N E R A L H O S P I T A LS Y S T E M N O R M A L1 0 : 2 2 : 3 4 A F R I J U L 1 8 , 2 0 0 3R E A D A D D R E S S : N 1 2 4 L 0 3 D 0 5 2A U T O M A T I C I N A C T I V EE L E V A T O R L O B B Y E A S T W I N GF I F T H F L O O R Z 0 0 5 H E A T ( A N A L O G )Z 0 0 5 , Z 0 2 7 , Z 0 6 6 , , ,, , , , ,V A L U E S : 0 1 1 % O F A L A R M ,1 0 : 2 2 : 3 4 A F R I J U L 1 8 , 2 0 0 3 B A C KTechnical Manuals Online! - http://www.tech-man.com