NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 33Installing Remote Printers and/or CRT InstallationEnter the CRT-2 setup menu by pressing and holding the key while pressing the Lock> key. Use arrow keys to move through the selections in each setup group; press the space barto view the options for each parameter. When finished programming all setup groups, press the key. To save all changes, press .Table 3.4 shows the standard settings for using the CRT-2 with the NFS-320/E/C; for one instancewhere these settings may change slightly see Section 3.11.4 “Connecting Multiple Printers, CRTs,or CRT/PRN Combination”. The basic settings for using the CRT-2 with NFS-320/E/C are:• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.3.11.4 Connecting Multiple Printers, CRTs, or CRT/PRNCombinationConnecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:NOTE: This section covers installation only; for information on how the CRT-2 functions as partof the fire alarm system, see the NFS-320/E/C Operations Manual.NOTE: The CRT cannot be connected at the same time as the network.Function Key CRT-2 ParametersF1: Quick(“Read Status” key)Emulation=CRT-2Comm Mode=Full DuplexEnhanced=OnEIA Baud Rate=9600Aux Baud Rate=9600Language=U.S.EIA Data Format=8/1/NAux Data Format=8/1/NHost/Printer=EIA/AuxF2:Genrl(“Alter Status” key)Emulation=CRT-2Auto Font Load=OnMonitor Mode=OffHost/Printer=EIA/AuxEnhanced=OnAuto Page=OffBell Volume=09Auto Wrap=OffAuto Scroll=OnWarning Bell=OnF3: Displ(“Prog” key)Page Length=24Display Cursor=OnColumns=80Scroll=JumpScreen Length=26 LinesCursor=Blink LineWidth Change Clear=OffRefresh Rate=60 HzScreen Video=NormalAuto Adjust Cursor=OnSpeed=NormalOverscan Borders=OffF4: Kybd(“Spl Funct” key)Language=U.S.Keyclick=OffKey Lock=CapsChar Set Mode=ASCIIKey Repeat=OffKeyboard Present=YesKey Mode=ASCIIMargin Bell=OffF5: Keys(“Prior” key)Enter Key=Alt Key=MetaPound Key=U.S.Return Key=Disconnect=PauseBackspace=/Desk Acc=DisabledF6: Ports(“Next” key)EIA Baud Rate=9600Aux Baud Rate=9600EIA Xmt=Xon-XoffAux Xmt=Xon-XoffEIA Break=OffAux Break=OffEIA Data Format=8/1/NAux Data Format=8/1/NEIA Recv=Xon-Xoff(XPC)Aux Recv=Xon-Xoff(XPC)EIA Modem Control=OffAux Modem Control=OffEIA Parity Check=OnAux Parity Check=OnEIA Xmt Pace=BaudAux Xmt Pace=BaudEIA Disconnect=2 secAux Disconnect=2 secF7: Host(“Auto Step” key)Comm Mode=Full DuplexRecv =IgnoreSend Block Term=Local=OffSend ACK=OnNull Suppress=OnRecv =Send Line Term=F8: Print(“Activ Signal” key)Prnt Line Term= Prnt Block Term= Secondary Recv=OffF9: Emul Attribute=PageWPRT Intensity=DimWPRT Blink=OffStatus Line=OffBright Video=OffWPRT Reverse=OffDisplay NV Labels=OffFkey Speed=NormalPage Edit=OffWPRT Underline=OffSave Labels=OnF10 Setup Group F10 does not affect communications with the control panel.F11 Setup Group F11 does not affect communications with the control panel.F12: Prog(“Ack Step” key)Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~GF8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~QTable 3.4 Standard CRT-2 Settings for Use with NFS-320/E/C
PreviousNext |