Panasonic Electric Works Nordic ABMEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x84 Selective Fire alarm presentationNormally all fire alarms will be presented in the c.i.e:s, ext. FBP:s andPresentation units, etc. There are some possibilities to select whichalarms that shall be presented in each unit. It is also programmable, ifthe fire alarm presentation shall be according to EN54, i.e. when onlyone point in a zone is in alarm status it will be presented as a pointalarm (zone and address), else presented as a zone alarm.4.1 Alert Annunciation Units 1735 & 1736The alarm presentation in an AA unit will be like in the c.i.e. that theAA unit is connected to, i.e. point alarm or zone alarm presentation.See Operating Instructions, chapter "Fire alarm" for the systemrespectively.Via Win512 / Win128 / Win512 G3, it is possible to select whichalarms that shall be presented in the AA unit respectively. Forexample, if there are many buildings in an installation, the AA unit inone specific building shall only present alarms activated within thisbuilding.The following, so called operands are available (CU alternatives notvalid for EBL128):1. Control unit (CU)2. Consecutive control units (CU1, CU2)3. Zone (zone)4. Consecutive zones (zone1, zone2)5. Zone – address (zone, addr)6. Consecutive zone – addresses (zone1, addr1, zone2, addr2)Explanations:1. CU = Control unit number (c.i.e. no. 00-29)2. CU1 = The first control unit number in the sequence. CU2 = Thelast control unit number in the sequence.3. zone = Zone number (001-999) In EBL128 (01-32).4. zone1 = The first zone number in the sequence. zone2 = The lastzone number in the sequence.5. zone, addr = Zone number and address within the zone (001, 01 –999, 99)6. zone1, addr1 = The first zone number and address in the sequence.zone2, addr2 = The last zone number and address in the sequence.Up to 50 operands can be used to make a, so called selector for an AAunit. Here follows a selector example:Control unit (00), Consecutive zones (100, 500), Zone – address(900, 01) In this AA unit will only be presented alarms that originfrom the c.i.e. no. 00 or from zone 100 up to and including zone 500or from the alarm point 900-01.