Panasonic Electric Works Nordic ABMEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x166 SW mode & Address settingAlert Annunciation Unit 1735 can run in SW mode 1735 - 1587 only.It shall also have a unique address on the RS485 line connected to the1587 board in the EBL512 c.i.e. See EBL512 Planning Instructions.Alert Annunciation Unit 1736 can run in SW mode 1736 - 1587 only.It shall also have a unique address on the RS485 line connected to the1587 board in the EBL512 c.i.e. See EBL512 Planning Instructions.The SW mode 1736 – 1587 shall be used in system EBL128 and anoptional RS485 transceiver component 4552 is required on the mainboard in the EBL128 c.i.e. It shall also have a unique address on theRS485 line connected to the main board connector "J1". See EBL128Planning Instructions.The SW mode 1736 – 1587 shall be used in system EBL512 G3. Itshall also have a unique address on the RS485 line connected to themain board connector "J4". See EBL512 G3 Planning Instructions.6.1 SW mode settingA brand new AA unit has no SW mode. It is factory set to "Notselected" (and is hereby not addressable). When it is powered it willautomatically be ready for the "SW mode setting".As an alternative, an AA unit in operation15 can be ready for the "SWmode setting" via the jumper "J4" in the unit. See the followingchapter.When the AA unit is ready for the "SW mode setting" this is indicatedby the LED "L2" (Alarms queued). The back-light is turned on andthe following information is shown in the display:MODE SETTING! Change = BlackType: xxxxxxxxxxxx Store = YellowXXXXXXXXXXXX can be changed to one of the following:- 1735 – 1587 (1735 only)- 1736 - 1587 (1736 only)- 1826 – 1587 2nd Cab- 1826 – 1582 2nd Cab- 1826/28 - 1587- 1826/28 - 1582- 1728 - 1587- 1728 - 1582- Not selectedScroll to the wanted SW mode with the push button "P1" (black).Store the selected SW mode with the push button "P2" (yellow) and15 Or when a unit, not in operation but with the mode and address set before,is powered.