4312.4 Airflow Direction1. There is one type of airflow, vertical airflow (directed by horizontal vane).2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heatexchanger temperature and intake air temperature) and manual (angles of direction can be adjusted usingremote control).12.4.1 Vertical AirflowOperation Mode Airflow Direction Upper Vane Angle (°)1 2 3 4 5HeatingAuto with Heat Exchanger A Upward fix 20B Downward fix 58Temperature C Upward fix 20Manual 20 33 45 58 70Cooling Auto 20 ~ 70Manual 20 33 45 58 70Soft Dry Auto 20 ~ 70Manual 20 33 45 58 701. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as statedabove. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1below. When the air conditioner is stopped using remote control, the vane will shift to close position.2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positionsof the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to closeposition.12.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode) Purposeo To provide quiet cooling operation compare to normal operation. Control conditiono Quiet operation start condition When “POWERFUL/QUIET” button at remote control is pressed twice.POWERFUL/QUIET LED illuminates.o Quiet operation stop condition When one of the following conditions is satisfied, quiet operation stops: POWERFUL/QUIET button is pressed again. Stop by OFF/ON switch. Timer “off” activates. When quiet operation is stopped, operation is shifted to normal operation with previous setting. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode. During quiet operation, if timer “on” activates, quiet operation maintains. After off, when on back, quiet operation is not memorised. Control contentso Fan speed is changed from normal setting to quiet setting of respective fan speed.Fan speed for quiet operation is reduced from setting fan speed.ACBIndoor Heat ExchangerTemperature58°C (136.4°F)50°C (122°F)0°21345Side View(Close position)Figure 130°C (86°F)37°C (98.6°F)Figure 2