4913.2.5 Dew Prevention Control 1 To prevent dew formation at indoor unit discharge area. This control will be activated if:o Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.o When Cooling or Dry mode is operated more than 20 minutes or more. This control stopped if:o Compressor stopped.o Remote control setting changed (fan speed / temperature).o Outdoor air temperature and indoor intake temperature changed. Fan speed will be adjusted accordingly in this control.13.2.6 Odor Cut Control To reduce the odor released from the unit.o Start Condition AUTO FAN Speed is selected during COOL or DRY operation. During freeze prevention control and timer preliminary operation, this control is not applicable.o Control content Depends on compressor conditions:1. Compressor OFF → Compressor ON.The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.2. Compressor ON → Compressor OFF.The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.13.3 Protection Control For Heating Operation13.3.1 Intake Air Temperature ControlCompressor will operate at limited freq., if indoor intake air temperature is 30°C (86°F) or above.13.3.2 Outdoor Air Temperature Control The Max current value is regulated when the outdoor air temperature rise above 14°C (57.2°F) in order to avoidcompressor overloading. The compressor will be stopped to avoid compressor overloading.Current RegulatedFree Within Max LimitOutdoor air temperature14°C (57.2°F)12°C (53.6°F)COMP. OFFCOMP. ON-15°C (5°F)-17°C (1.4°F)OutdoorAir Temperature