2. Manual horizontal airflow direction can be set using remote controller; the angles of the vane are as stated below and thepositions of the vane are as Figure 2 above.Pattern 1 2 3 4 5Airflow DirectionPatterns at RemoteControllerVane Angle (°) 90 55 70 110 1258.1.8. Automatic Mode OperationThis mode can be set using remote controller and the operation is decided by remote controller setting temperature, indoor intakeair temperature and outdoor air temperature.During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 20 seconds to detectthe indoor intake and outdoor air temperature. The operation mode is decided based on below chart.Values of T1, T2, and T3 depend on remote controller setting temperature, as shown in below table. After the adjustment of T1,T2 and T3 values, the operation mode for that particular environment and remote controller setting is judged and performed, basedon the above operation mode chart, every 30 minutes. Heating mode operation will be performed, however, if deice operation isdetected.Remote Controller Setting Temperature (°C) T1 T2 T316 ~ 18 +10 +8 -519 ~ 22 +8 +7 -723 ~ 26 +7 +6 -727 ~ 30 +6 +5 -8There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or viceverse.Operation Mode change from Temperature shifts (°C)Cooling/Soft Dry → Heating -2Heating → Cooling/Soft Dry +2Example of operation mode chart adjustment:From the above table, if remote controller setting temperature = 25,T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 1825CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oywww.ilmalämpöpumput.com