3714.4. Error Codes TableNote:“O” - Frequency measured and fan speed fixed.The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heardfollowing by pressing the “RESET” button at remote controller.Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to ErrorCodes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound ischanged from one “beep” to four “beep” sounds.Diagnosisdisplay Abnormality / Protection control AbnormalityJudgementEmergencyoperation Primary location to verifyH00 No abnormality detected — Normal operation —H11 Indoor / outdoor abnormal communication > 1 min after startingoperationIndoor fan operationonly• Internal / external cable connections• Indoor / Outdoor PCBH12 Connection capability rank abnormal — — —H14 Indoor intake air temperature sensorabnormality Continue for 5 sec. — • Intake air temperature sensor(detective or disconnected)H15 Outdoor compressor temperature sensorabnormality Continue for 5 sec. — • Compressor temperature sensor(detective or disconnected)H16 Outdoor Current Transformer open circuit — — • Outdoor PCB• IPM (Power transistor) moduleH19 Indoor fan motor merchanism locked — — • Indoor PCB• Fan motorH23 Indoor heat exchanger temperaturesensor abnormality Continue for 5 sec. O(Cooling only)• Heat exchanger temperature sensor(defective or disconnected)H26 Ionizer breakdown — — • IonizerH27 Outdoor intake air temperature sensorabnormality Continue for 5 sec. O • Outdoor temperature sensor(defective or disconnected)H28 Outdoor heat exchanger temperaturesensor abnormality Continue for 5 sec. O • Outdoor heat exchanger temperaturesensor (defective or disconnected)H30 Outdoor discharge air temperature sensorabnormality Continue for 5 sec. — • Outdoor temperature sensor(defective or disconnected)H33 Indoor/Outdoor wrong connection — — • Indoor/Outdoor supply voltageH38 Indoor / outdoor mismatch (brand code) — — —H97 Outdoor fan motor mechanism locked 2 times occurancewithin 30 minutes — • Indoor PCB• Fan motorH98 Indoor high pressure protection — — • Air filter dirty• Air circulation short circuitH99 Indoor heat exchanger anti-freezingprotection — — • Insufficient refrigerant• Air filter dirtyF11 Cooling / Heating cycle changeoverabnormality4 times occurancewithin 30 minutes — • 4-way valve• V-coilF90 PFC control 4 times occurancewithin 10 minutes — • Voltage at PFCF91 Refrigeration cycle abnormality 2 times occurancewithin 20 minutes — • No refrigerant(3-way valve is closed)F93 Compressor rotation failure — — • CompressorF95 Cool high pressure protection 4 times occurancewithin 20 minutes — • Outdoor refrigerant circuitF96 IPM (power transistor) overheatingprotection — —• Excess refrigerant• Improper heat radiation• IPM (Power transistor)F97 Outdoor compressor overheatingprotection4 times occurancewithin 10 minutes — • Insufficient refrigerant• CompressorF98 Total running current protection 3 times occurancewithin 20 minutes — • Excess refrigerant• Improper heat radiationF99 Outdoor Direct Current (DC) peakdetection7 times occurancecontinuously —• Outdoor PCB• IPM (Power transistor)• Compressor