2812. Operation Control12.1 Basic Function12.1.1 Internal Setting TemperatureOnce the operation starts, remote control setting temperature will be taken as base value for temperature shiftingprocesses. These shifting processes are depending on the air conditioner settings and the operation environment.The final shifted value will be used as internal setting temperature and it is updated continuously whenever theelectrical power is supplied to the unit.12.1.2 Cooling Operation12.1.2.1 Thermostat control• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5к• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >Compressor OFF point.12.1.3 Soft Dry Operation12.1.3.1 Thermostat control (The same as Cooling mode)12.1.4 Heating operation12.1.4.1 Thermostat control• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0к• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature<Compressor OFF point.12.1.5 Automatic Operation1. Once AUTO mode is selected, operation mode is determined by set temperature of remote control, indoorintake temperature and outdoor temperature.2.During operating mode judgment, indoor fan runs at minLo- fan speed and outdoor fan runs in the purpose ofdetecting the intake air temperature and outdoor air temperature (for 30 seconds)Remote Control Setting Temp. (16к~30Indoor Air Temperature ShiftingOutdoor Air Temperature ShiftingInternal Setting TemperaturePowerful Temperature Limit Checking ( Min:16 к;Internal Setting Temperature