25.11. Forced operation during restartThe compressor will not stop operating for 3 minutes after cooling mode operation starts, even if the indoor unit thermostat turnsoff.(However, the compressor will stop operating during this time if the indoor unit air intake temperature drops to 16°C and belowduring cooling mode operation.)25.12. Louvre control (models with louvre)1. When main power is turned onWhen the power is turned on, indoor unit louvre position detection is carried out twice and then the indoor unit louvre stops.2. During initial operationWhen the OFF/ON button is pressed to start the operation, the louvre moves through one full cycle, and then swingsautomatically (if AUTO has been set using the remote control) or moves to the setting angle (if MANUAL has been set usingthe remote control).3. When operation stopsWhen the OFF/ON button is pressed to stop the operation, the louvre moves through one full cycle, and then stops in the downposition, regardless of the remote control setting.4. When thermostat is offWhen operation is stopped by the indoor thermostat, the louvre moves through one full cycle, and then stops in the horizontalposition, regardless of the remote control setting.25.13. Outdoor unit fan excess heat dissipation control1. When the operation is stopped while the compressor is in operation, the outdoor fan will run at SUPER HI fan speed forapproximately 60 seconds and then stops.25.14. Discharge temperature control1. OperationWhen the discharge temperature sensor detects a temperature of 100°C or higher during cooling mode operation, the liquidbypass valve will be turned on.2. CancellingWhen the discharge temperature sensor detects a temperature of 70°C or lower, the liquid bypass valve will be turned off.69