2511. Installation Instruction11.1 Select The Best Location If an awning is built over the unit to prevent directsunlight or rain, be careful that heat radiation fromthe condenser is not obstructed. There should not be any animal or plant whichcould be affected by hot air discharged. Keep the spaces indicated by arrows from wall,ceiling, fence or other obstacles. Do not place any obstacles which may cause ashort circuit of the discharged air.Refrigerant piping sizeOutdoor Unit CU-3TZ52***Liquid - side ø 6.35 t0.8Gas - side ø 9.52 t0.8Table AMODELMaximum TotalPiping Lengthfor add. Gas(m)AdditionalRefrigerant(g/m)Indoor Amin (m 2 )1.8 m forwallmounted2.5 m forwallmountedCU-3TZ52*** 30 20 5.96 3.09 If total piping length of all indoor units exceed themaximum total length listed above, additionallycharge with 20 g of refrigerant (R32) for eachadditional meter of piping.Amin = (mc / (2.5 x (LFL)(5/4) x h0)) ²Amin = Required minimum room area, in m 2mc = Refrigerant charge amount in appliance, in kgLFL = Lower flammable limit (0.306 kg/m 3)h0 = Installation height of the appliance: (1.8 m for wall mounted is standard referenceinstalled height): (2.5 m for wall mounted is recommendedinstalled height give by manufacturer)• This illustration is for explanation purposes only.3/8" Gas side piping ( )1/4" Liquid side piping ( )Additional drain hose ( )Connecting cable ( )Power supply cord ( )Outdoor Unit Installation DiagramInstallation parts youshould purchase ( )It is advisable to avoidmore than 2 blockagedirections. For betterventilation & multiple-outdoor installation,please consult authorizeddealer/specialist.* Note:Respective indoor unit installation procedure shall refer toinstruction manual provided in the indoor unit packaging.Allowable piping lengthOutdoor Unit CU-3TZ52***Allowable piping length of each indoor unit (min. ~ max.) 3 m ~ 25 mAllowable total piping length of all indoor unit 50 m or lessHeight difference between indoor andoutdoor unitOutdoor unit located on upper side 15 m or lessOutdoor unit located otherwise 7.5 m or lessHeight difference between indoor unit Outdoor unit located on upper side 7.5 m or lessOutdoor unit located otherwise 15 m or less