3914.13 Compressor Protection Control (Gas leak detection control 1) Control start conditionso For 5 minutes, the compressor continuously operates and total current is low.o During Cooling or Soft Dry operation:Indoor intake temperature — indoor piping temperature is below 4°C.o During Heating operation:Indoor pipe temperature — indoor intake temperature is below 3°C.o Not during deice control.o Compressor ON with maximum frequency. Control contento Compressor stops (and restart after 3 minutes)o If the conditions above happen 4 times within 60 minutes, the unit will stop operation (“F91” is indicated).14.14 Compressor Protection Control (Gas leak detection control 2) This control detect gas leakage condition to prevent compressor damage. Control start conditiono All connected indoor units capability supply ON.o Compressor ON with maximum frequency.o Not during annual cooling.o Compressor discharge temperature high. Control contento Compressor OFF during this control (“F91” is memorized in EEPROM)o If the above conditions happen 2 times within 60 minutes, indoor units’ Timer LED will blinks (“F91” isindicated at all indoor units)14.15 Valve close detection control This control detects 3-way valve close condition to prevent damage to refrigerant cycle. Start conditions:o For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between -2°Cand 2°C continuously for 5 minutes after compressor ON at first cooling operation.o The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installationor after pump down. Control contento During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units) Error reset can be done by power supply reset or reset by using remote control.14.16 Compressor discharge high pressure protection control This control protect by using high pressure switch during operation. Start conditionso High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling orheating during compressor running. Control 1 contento Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If thiscondition happen 4 times within 30 minutes, “F94” is indicated.o After 30 minutes, counter is reset if this condition does not happen for 4 times. Control 1 stop conditionso Power supply reseto Reset by using remote control