103.2. CS-F24DTE5 CU-J24DBE81. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)ELECTRICAL DATA (50 Hz)ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F24DTE5 CU-J24DBE8RemoteControlCZ-RD513C (Wired)CZ-RL513T (Wireless)Cooling Capacity kW 6.6BTU/h 22,500Refrigerant Charge-less m 30Standard Air Volume for High Speed m 3 /min 17 60cfm 600 2120Outside Dimension (H x W x D) mm 210 x 1245 x 700 795 x 900 x 320inch 8-9/32 x 49-1/64 x 27-9/16 31-5/16 x 35-7/16 x 12-19/32Net Weight kg (lbs) 33 (73) 61 (135)PipingConnectionRefrigerant Gas mm (inch) O.D Ø 15.88 (5/8) Flared TypeLiquid mm (inch) O.D Ø 9.52 (3/8) Flared TypeDrain O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1Starting Method - Permanent Split CapacitorMotor Type - 2-pole 1 phase brushless motorRated Output kW - 1.8Fan Type, Number of Set Sirocco fan-4 Mix flow fan-1Motor Type 4-pole single phase induction motor 6-pole single phase induction motorRated Output kW 0.04 0.07Air-heat Exchanger (Row x Stage x FPI) Slit-fin type (2 x 12 x 18) Corrugate-fin type (1 x 36 x 21)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - FV50S (1130)Refrigerant (Charged) R410a kg (oz) - 1.35 (48)RunningAdjustmentControl Switch Wireless or Wired Remote Control -Room Temperature Thermostat -Noise Level dB (A) Cooling: 43/39 50/-Power LeveldBCooling: 60/56 66/-Moisture Removal L/h (Pt/h) 3.8 (8.0)EER W/W 2.56/2.51/2.46ITEM / MODEL Condition by ISO5151Volts V 380 400 415Phase Three Three ThreePower Consumption kW Cooling 2.58 2.63 2.68Running Current A Cooling 4.55 4.60 4.65Starting Current A 23 25 27Power Factor % Cooling 86 83 80Panasonic Power source AC, 3~380V, 400V, 415V 50Hz