20 (EN)Itemcode Set contents Set data06Flap settingDisables switching operation of airflow direction and disables the airflowdisplay.• 0000: Display andoperation enabled *• 0001:Display andoperation disabled07 Alarm output delay functionDelays the relay output ON when an alarm occurs.• 0000: No delay *• 0001 to 0015• 0001: 1 min,0015: 15 min(1-minute interval)09Password auto lockLocks the password during no operation when the password is temporarilyunlocked.• 0000: Auto lock not set• 0001: 5 min• 0006: 30 min(5-minute interval)*0A Screen auto offClears the LCD display during no operation.• 0000: Not set*• 0001: 30 min0CPeak cut functionSchedule peak cut/Schedule energy saving/External input peak cutSwitches among the 3 functions.• 0000: Schedule peak cut*• 0001: Schedule energy saving• 0002: External input peak cut0E Temp display settingSet the type of temperature display.• 0000: °C *• 0001: °F2F Password changeEnables changing the password for the password setting function.• 0000 to 9999:• 0000: *36Display of operation lock cancelling methodSet whether to display the operation lock cancelling method on the lockscreen while operation is locked. (For the lock screen, see the “PartNames” section in the Quick Reference.)• 0000: Displayed *• 0001: Not displayedNumber-of-controlled-units modeIn combination of the item code 03 “All/Zone mode” and the item code 05 “Centralcontrol/Remote control mode”, the following to modes can be set.Central control/Remote control modeControl targetCentral controlmode Remote control modeDisabling the settingfunction can beused.Disabling the setting functioncannot be used.• The Prohibit R/C setting isdisabled.Group ZoneNumber-of-controlled-units mode All mode All central control All remote control 1 to 64 1 to 4Zone 1 mode Zone 1 centralcontrol Zone 1 remote control 1 to 16 1Zone 2 mode Zone 2 centralcontrol Zone 2 remote control 17 to 32 2Zone 3 mode Zone 3 centralcontrol Zone 3 remote control 33 to 48 3Zone 4 mode Zone 4 centralcontrol Zone 4 remote control 49 to 64 4Setting (continued) *Factory default