10-210.1 Table of Specifications10.1.1 General SpecificationsItem DescriptionRated operating voltage 24V DCOperating voltagerange 21.6 to 26.4V DCC32C28 4ms at 21.6V, 7ms at 24V, 10ms at 26.4VAllowedmomentarypower off time C24 3ms at 21.6V, 5ms at 24V, 8ms at 26.4VAmbient temperature 0 to +55 °CStorage temperature −20 to +70°CAmbient humidity 30 to 85%RH (at25°C non-condensing)Storage humidity 30 to 85%RH (at25°C non-condensing)Between input/output terminals and power supplyterminal/function earthC32C28 Between input terminal and output terminal500VAC for1 minute Note)Between input terminals (X0 to X7)/input terminals (X8 toXF) and power supply terminal/function earth500VAC for1 minute Note)Between output terminals and power supplyterminal/function earth1500VAC for1 minute Note)Between input terminals (X0 to X7) and input terminals(X8 to XF)500VAC for1 minute Note)BreakdownvoltageC24Between input terminals (X0 to X7)/input terminals (X8 toXF) and output terminals1500VAC for1 minute Note)C32 Between input/output terminals and power supplyterminal/function earthC28 Between input terminal and output terminalBetween input terminals (X0 to X7)/input terminals (X8 toXF) and power supply terminal/function earthBetween output terminals and power supplyterminal/function earthBetween input terminals (X0 to X7) and input terminals(X8 to XF)InsulationresistanceC24Between input terminals (X0 to X7)/input terminals (X8 toXF) and output terminalsMin. 100MΩ(measuredwith a 500VDC megger)Vibration resistance 10 to 55 Hz, 1 cycle/min, double amplitude of 0.75 mm, 10 min on 3 axesShock resistance Shock of 98 m/s2 , 4 times on 3 axesNoise immunity 1000 Vp-p with pulse widths 50 ns and 1μs (based on in-housemeasurementsOperation condition Free from corrosive gases and excessive dustNote) Cutoff current : 10 mA However, excluding varister for protection. (Factory default setting value)