5-175.3 Reading Initialization InformationThe initialization information subsequent to the initialization processing of the current unit can be readfrom the shared memory. The initialization information notified area (Bank: 0, Addresses: 2D0H to 2DFH)should be read using the shared memory read instruction F150 (READ) and P150 (PREAD).Initialization information notified area (bank 0)Address Name Setting value and explanation2D0HInitializationprocessingcomplete code[Stored value] 0: Initialization processing was completed successfully.Any other value: Error code (initialization processing ended in an error)2D1H Source node IPaddress[Stored value] Source node IP address when initialization processing wascompleted successfully.- The source node address in the initialization information setting area iswritten.- The value is not entered until initialization processing has been completedsuccessfully.2D2H Source node IPaddress2D3HCommunicationfunction settingbetweennetworks[Stored value]0: Communication function setting between networks is not used.1: Communication function setting between networks is used.- The value is not entered until initialization processing has been completedsuccessfully.2D4HSource nodeMEWTOCOLstation number[Stored value] Source node MEWTOCOL station number when initializationprocessing has been completed successfully.- The source node MEWTOCOL station number in the initializationinformation setting area is written.- The value is not entered until initialization processing has beencompleted successfully.2D5H(lower word) Source nodeEthernetaddress(48 bits)[Stored value] Source node Ethernet address in the EEPROMExample: If 1.2.3.4.5.6 has been set:2D5H 0506H2D6H 0304H2D7H 0102H- The value is not entered until initialization processing has been completedsuccessfully.2D6H2D7H(higher word)