8.2 MEWTOCOL-COM Format8-78.2.2 MEWTOCOL-COM Response Format Response messageAfter PLC receives a command, it returns the processing result.(1) Header (start code) A “%” (ASCII code: H25) or “<” (ASCII code: H3C) must be at the beginning of a message. The response must start with the same header that was at the beginning of the command.(2) Station no.This is the station no. of the PLC that processed the command.(3) TextThe content of this varies depending on the type of command. If the processing is notcompleted successfully, an error code will be stored here, so that the content of the error canbe checked.(4) Check code This is a BCC (block check code) for error detection using horizontal parity. The BCC starts from the header and checks each character in sequence, using theexclusive OR operation, and converts the final result.(5) Terminator (end code)The message should end with "CR" (ASCII code: H0D).Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com