130Data identification Name Dataformat unit byte range R/WDI 3 DI 2 DI 1 DI 004 05 0241 Voltage THD alarm(phase) OUT2 X - 10:All,1:Phase1(line1-2),2:Phase2(line2-3),3:Phase3(line3-1)R/W42 Under current alarm(phase) OUT1 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/W43 Under current alarm(phase) OUT2 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/W44Current unbalancingalarm(ON threshold)OUT1XXX.XX 0.01% 3 0 to 99999 R/W45Current unbalancingalarm(OFF threshold)OUT1XXX.XX 0.01% 3 0 to 99999 R/W46Current unbalancingalarm(ON threshold)OUT2XXX.XX 0.01% 3 0 to 99999 R/W47Current unbalancingalarm(OFF threshold)OUT2XXX.XX 0.01% 3 0 to 99999 R/W48Voltage unbalancingalarm(ON threshold)OUT1XXX.XX 0.01% 3 0 to 99999 R/W49Voltage unbalancingalarm(OFF threshold)OUT1XXX.XX 0.01% 3 0 to 99999 R/W4AVoltage unbalancingalarm(ON threshold)OUT2XXX.XX 0.01% 3 0 to 99999 R/W4BVoltage unbalancingalarm(OFF threshold)OUT2XXX.XX 0.01% 3 0 to 99999 R/W4C Reactive power alarm(ON threshold) OUT1 XXXXXXX.X 0.1kvar 4 0 to 29999999 R/W4D Reactive power alarm(OFF threshold) OUT1 XXXXXXX.X 0.1kvar 4 0 to 29999999 R/W4E Reactive poweralarm(phase)OUT1 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3,5:total R/W4F Reactive power alarm(ON threshold) OUT2 XXXXXXX.X 0.1kvar 4 0 to 29999999 R/W50 Reactive power alarm(OFF threshold) OUT2 XXXXXXX.X 0.1kvar 4 0 to 29999999 R/W51 Reactive power alarm(phase)OUT2 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3,5:total R/W52 Apparent power alarm(ON threshold) OUT1 XXXXXXX.X 0.1kVA 4 0 to 29999999 R/W53 Apparent power alarm(OFF threshold) OUT1 XXXXXXX.X 0.1kVA 4 0 to 29999999 R/W54 Apparent power alarm(phase)OUT1 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3,5:total R/W55 Apparent power alarm(ON threshold) OUT2 XXXXXXX.X 0.1kVA 4 0 to 29999999 R/W56 Apparent power alarm(OFF threshold) OUT2 XXXXXXX.X 0.1kVA 4 0 to 29999999 R/W57 Apparent power alarm(phase)OUT2 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3,5:total R/W58 Over frequency alarm(ON threshold) OUT1 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W59 Over frequency alarm(OFF threshold)OUT1 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W5A Over frequency alarm(phase)OUT1 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/WPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com