131Data identification Name Dataformat unit byte range R/WDI 3 DI 2 DI 1 DI 004 05 025B Over frequency alarm(ON threshold) OUT2 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W5C Over frequency alarm(OFF threshold) OUT2 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W5D Over frequency alarm(phase)OUT2 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/W5E Under frequency alarm(ON threshold) OUT1 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W5F Under frequency alarm(OFF threshold) OUT1 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W60 Under frequency alarm(phase)OUT1 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/W61 Under frequency alarm(ON threshold) OUT2 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W62 Under frequency alarm(OFF threshold) OUT2 XXX.XX 0.01Hz 3 0.01 to 100.00 R/W63 Under frequency alarm(phase)OUT2 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/W64 Power demand alarm(Power type) OUT1 X - 10: active power,1: reactive power,2: apparent power,3: active power(export),4: reactive power(export)R/W65 Power demand alarm(ON threshold) OUT1 XXXXX.XXX 0.001 4 0 to 99999.999 R/W66 Power demand alarm(OFF threshold) OUT1 XXXXX.XXX 0.001 4 0 to 99999.999 R/W67 Power demand alarm(target) OUT1 XXXXX.XXX 0.001 4 0 to 99999.999 R/W68 Power demand alarm(hysteresis) OUT1 XXX 1% 2 0 to 100% R/W69 Power demand alarmstart-time OUT1 XX 1min, 1 1 to 30 R/W6A Power demand alarm(Power type) OUT2 X - 10: active power,1: reactive power,2: apparent power,3: active power(export),4: reactive power(export)R/W6B Power demand alarm(ON threshold) OUT2 XXXXX.XXX 0.001 4 0 to 99999.999 R/W6C Power demand alarm(OFF threshold) OUT2 XXXXX.XXX 0.001 4 0 to 99999.999 R/W6D Power demand alarm(target) OUT2 XXXXX.XXX 0.001 4 0 to 99999.999 R/W6E Power demand alarm(hysteresis) OUT2 XXX 1% 2 0 to 100% R/W6F Power demand alarmstart-time OUT2 XX 1min, 1 1 to 30 R/W70 Current demand alarm(ON threshold)OUT1 XXX.X 0.1% 2 0 to 1200 R/W71 Current demand alarm(OFF threshold)OUT1 XXX.X 0.1% 2 0 to 1200 R/W72 Current demand alarm(phase)OUT1 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/W73 Current demand alarm(ON threshold)OUT2 XXX.X 0.1% 2 0 to 1200 R/W74 Current demand alarm(OFF threshold)OUT2 XXX.X 0.1% 2 0 to 1200 R/W75 Current demand alarm(phase)OUT2 X - 1 0:All,1:Phase1,2:Phase2,3:Phase3 R/WPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com