INSTALLATION44 Installation Manual2.4 FRAME GROUND CONNECTIONIMPORTANT!!!Connect the frame of the main unit to the ground.1. Loosen the screw.2. Insert the grounding wire.3. Tighten the screw.4. Connect the grounding wire to the ground.In most of North America, the ground provided by the "Third wire ground" at the commercialor residential power outlet will be satisfactory. However, in some cases this ground may beinstalled incorrectly. Therefore, the following test procedure should be performed.Test Procedure1. Obtain a suitable voltmeter and set it for a possible reading of up to 250 V AC.2. Connect the meter probes between the 2 main AC voltage points on the wall outlet. Thereading obtained should be 108 V AC-132 V AC.3. Move one of the meter probes to the third prong terminal (GND).Either the same reading or a reading of 0 V should be obtained.4. If a reading of 0 V at 1 terminal and a reading of 108 V AC-132 V AC at the other terminalis not obtained, the outlet is not properly grounded. This condition should be corrected bya qualified electrician (per article 250 of the National Electrical Code).5. If a reading of 0 V at 1 terminal and a reading of 108 V AC-132 V AC at the other terminalis obtained, then set the meter to the "OHMS/RX1" scale, place 1 probe at the GNDTerminal and the other probe at the terminal which gave a reading of 0 V. A reading of lessPanasonicPanasonicTo ground