88-13. Emergency OperationUse [Emergency Operation] in the following situations when there is an urgent need.• When the remote control's batteries have failed.• When the remote control is broken.• When the remote control is lost.1. Press [Emergency Operation] of the receiverIf the indoor temperature is 24°C or greater when the unit starts running,it will act as a cooler.If the indoor temperature is less than 24°C when the unit starts running,it will act as a heater.2. If you press , the wind direction automatically oscillates up and down.Stop: press [Emergency Operation] of the receiver again.NOTE• The Test Run/On and Test/On switches are for use when the unit is installed and test run. It is not for normaluse.• If the [Normal/Stop ALL] switch is on Stop ALL , the unit cannot receive signals from the remote control.CZ-RWSC2128-14. Miscellaneous SettingsA variety of changes can be made to settings, depending on the indoor unit being used.Wind direction (flap) indicator, operation mode indicator, time display (24 hour, AM/PM), heat max temp• For information about the flap function, refer to the users’ manual of the unit being used.• (These settings are saved in nonvolatile memory in the remote control, so even when its batteries are changed,the settings do not have to be made again.)• First check the display of the remote control when the unit is stopped and then make any desired settings.How to Operate• is pressed the remote control’s display changes.•While holding down the buttons below, every timeWhatever is being displayed when you release is set.Setting Item Operation Button Setting Content Remote Control DisplayRemote control flap displaysetting for whenis pressedPresswhile pressingModels with movable flapsSwing only modelsenoNModels w/o lampsRemote control operationmode display setting whenis pressedPresswhile pressingHeat Pump (with Auto)Heat Pump (without Auto)Dedicated air conditionerClock display settingPresswhile pressing24 HourAM/PMMax possible temperaturesetting in the Heat modePresswhile pressingMaximum heatingtemperaturerange is 26°C – 30°C8-9