19617.3 Wired Remote Control Local Setting Mode• During unit off, press the TEST RUN button for 5 seconds to enter LOCAL MODE.• Press Temperature Up / Down button to select Mode No.• Press Timer SELECT button to enter setting mode.• Press Timer Up / Down button to select setting value.• Press Timer SET button to confirm the selection.• Press TEST RUN button to exit LOCAL SETTING MODE. If no operation is performed for 30 seconds, exitLOCAL SETTING MODE.ModeNo. Items Setting valueIndividualSettingNote 1)SettingvaluememoryterminalNote 2)00 Centralized control address 000 – 200: Address 0 – Address 200 ○ I01 Fan speed up 000: OFF 001: ON I000: Execute Reset(Level 0)Nighttime low noise001 – 003: Level 1 – Level 3Nighttime low noise ON time 0:00 23.50 (10 minutes interval)02Nighttime low noise OFF time 0:00 23.50 (10 minutes interval)R000: Default control001: 10 seconds fan sampling operation03 Thermostat OFFindoor fan control002: Fixed fan speed operation○ I000: default Thermostat OFF point (ΔD)001: Cool = ΔD+2°C, Heat = ΔD-2°C002: Cool = ΔD+4°C, Heat = ΔD-4°C003: Cool = ΔD-2°C, Heat = ΔD+2°C04 Thermostat OFFpoint adjustment004: Cool = ΔD-4°C, Heat = ΔD+4°C○ I000: Clear address06 Outdoor unit address 001 – 199: Address 1 - Address 199 ○ I10 Group address reset 000: Non-processed 001: Execute Reset Note 3)11 Thermistor selection 000: Non-processed 001: Remote control R000: OFF 001: ON(no-interlocking)12 Ventilation unit control 002: ON(OFF coupling)003: ON(ON/OFF coupling)RNote 1) Mark ○ in the column of the “Individual setting” shows a setting item individually made for each connectedindoor unit.Note 2) “R” represents remote control and I “indoor unit”.Note 3) Start the setting from the setting value 000.17.3.1 Fan Speed Up• This control can increase the fan speed of indoor unit with DC motor.• When enable, the HIGH fan speed setting at Remote Control, indoor unit fan tap changed from Hi to SHi.