Page 187033-277I July 7, 2011R3100 Wood Stove Series (ACC)Chimney Height / Rise and RunThis product was designed for and tested on a 6 inch (152mm)chimney, 14 to 16 feet (420-480cm) high, (includes stoveheight) measured from the base of the appliance. The furtheryour stack height or diameter varies from this configuration,the possibility of performance problems exists.Chimney height may need to be increased by 2 - 3% pereach 1000 feet above sea level. It is not recommended touse offsets or elbows at altitudes above 4000 feet above sealevel or when there are other factors that affect flue draft.C. Installing Chimney ComponentsChimney ConnectorSingle wall connector or stove pipe.This must be at least 24 gauge mild steel or 26 gauge bluesteel. The sections must be attached to the appliance and toeach other with the crimped (male) end pointing toward thestove. All joints, including the connection at the flue collar,should be secured with 3 sheet metal screws. Make sureto follow the minimum clearances to combustibles. Wherepassage through the wall, or partition of combustible con-struction is desired in Canada, the installation shall conformto CAN/CSA-B365.Factory-built listed chimney connector (vented).A listed connector (vented) must be used when installing thisunit in a mobile home. The listed connectors must conformto each other to ensure a proper fit and seal.Flue GasDirectionCrimpedEndTowardStoveSecure pipe sections with aminimum of 3 screwsFigure 18.2 Chimney Connector (Stove Pipe)WARNING• DO NOT CONNECT THIS UNIT TO A CHIM-NEY FLUE SERVICING ANOTHER APPLI-ANCE.• DO NOT CONNECT TO ANY AIR DISTRI-BUTION DUCT OR SYSTEM.May allow flue gases to enter the house.Asphyxiation Risk.Improper installation, adjustment, alteration, service ormaintenance can cause injury or property damage. Referto the owner’s information manual provided with this appli-ance. For assistance or additional information consult aqualified installer, service agency or your dealer.WARNINGFire Risk.Inspection of Chimney:• Chimney must be in good condition.• Meets minimum standard of NFPA 211• Factory-built chimney must be 6 inch(152mm) UL103 HT.WARNINGWARNINGONLY use connector:• Within the room, between appliance and ceiling or wall.Connector shall NOT pass through:• Attic or roof space• Closet or similar concealed space• Floor or ceilingMaintain minimum clearances to combustiblesFire Risk.Follow Chimney Connector Manufacturer’sInstructions for Proper Installation.Chimney FlueLinerFireclayLiner orEquivalentMasonry ChimneyConstructed to NFPA 211Wall SpacerWall BandTrim CollarChimneyConnector1 inch (25mm) AirSpace to ChimneySectionMin. Clearance2 inch (51mm)Min. Chimney Clearance toWall Spacer andCombustibles - 2 inch (51mm)Chimney SectionFigure 18.1Solid Pack Chimney with Metal Supports as aThimble (Cont’d)