PX3TS Transfer Switch Quick Setup Guide 6QSG-PX3TS-0D-v3.1-E 255-80-0032-00 RoHSFor example, 192.168.84.4 cycles in this sequence:192, 168, 84, 4Note: If your network only supports IPv6 or static IPv4addresses, the IP address must be configured using anRS-232 or USB port. See Addendum (on page 7) forinstructions.Step 3: Log in to the PX3TS Web Interface1. Open a web browser and type the IP address of thePX3TS device.2. The default credentials are: user admin, password raritan.3. Click Login. The PX3TS home page displays.4. Change the password if prompted.Step 4: PX3TS Web Configuration Overview1. From the PX Explorer pane, click the Transfer Switch icon.2. Click Setup to configure the transfer options.3. Click Power Quality Setup to configure power quality.Transfer Options Setup1. Enable/disable the front panel Manual Transfer button.2. Enable/disable automatic retransfer. Retransfer is thetransfer back to normal operation when preferred inletpower is restored.3. Enter the time (seconds) preferred inlet power must be inthe normal state before retransfer occurs.4. Enable/disable retransfer when inlets are out of phase.5. (Optional) Thresholds for inlet phase angle differencereporting. Values do not affect phase sync detection ortransfers.Power Quality SetupInlet power quality state (normal/warning/critical) is derivedfrom the inlet's voltage and frequency quality - whichever islower. If voltage or frequency is critical, power quality iscritical. If either is warning, quality is warning. When both arenormal, power quality is normal.PX3TS transfers to standby operation when preferred inletpower quality goes critical and retransfers to normal operationwhen power quality returns to normal. The warning state doesnot cause transfers and is intended as an early warningindication of a possible problem.When quality goes from better to worse, the state change issaid to assert. You configure how long the quality must remainin the worse state before the state change actually occurs.When quality goes from worse to better, the state change issaid to deassert. You configure the hysteresis - how much thequality must be better than the threshold - before the statechange occurs.Voltage and frequency configuration is identical.1. Enter upper and lower thresholds for warning and critical.2. Enter assertion times (seconds).