SECTION O: POST START-UP CHECKCheck off steps as completed:1. Boiler and heat distribution units or storage tank filled with water?2. Automatic air vent, if used, open two full turns during venting procedure?3. Air purged from system?4. Air purged from gas piping? Piping checked for leaks?5. Followed start-up procedure for proper start-up?6. Is burner flame visible?7. Test safety controls: If boiler is equipped with a low water cutoff or additional safety controls, test for operation asoutlined by manufacturer. Burner should be operating and should go off when controls are tested. When safety devicesare restored, burners should reignite after pre-purge time delay.8. Test limit control: While burner is operating, move indicator on high limit control below actual boiler watertemperature. Burner should go off while blower and circulator continue to operate. Raise setting on limit control aboveboiler water temperature and burner should reignite after pre-purge time delay..9. Test ignition system safety device:∑ Turn on manual gas valve. Turn power on.∑ Set thermostat to call for heat.∑ When the unit is in operation. Disconnect combustion air blower pressure switch, burner should go offimmediately.∑ Wait 5 minutes.∑ Reconnect combustion air pressure switch, burner should reignite after pre-purge time delay.10. To restart system, follow lighting instructions in Section O.11. High limit control set to design temperature requirements of system?For multiple zones: flow adjusted as required in each zone?12. Boiler cycled with thermostat? Raise to highest setting and verify boiler goes through normal start-up cycle.Reduce to lowest setting and verify boiler goes off.13. Observed several operating cycles for proper operation?14. Set room thermostat or tankstat to desired temperature?15. Reviewed all instructions shipped with this boiler with owner or maintenance person, returned to envelopeand given to owner or placed in pocket inside front panel on boiler?59