P36-10 Zero Clearance Direct Vent Gas Fireplace | 33|33installationPILOT ADJUSTMENTPeriodically check the pilot flames. Correctflame pattern has three strong blue flames:1 flowing around the thermopile, 1 aroundthe thermocouple and 1 flowing across theburner (it does not have to be touching theburner).Note: If you have an incorrect flame pat-tern, contact your Regencydealer forfurther instructions.Incorrect flame pattern will have small,probably yellow flames, not coming intoproper contact with the rear burner orthermopile or thermocouple.GAS PIPE PRESSURETESTINGThe appliance must be isolated from the gassupply piping system by closing its individualmanual shut-off valve during any pressuretesting of the gas supply piping system attest pressures equal to or less than 1/2 psig.(3.45 kPa). Disconnect piping from valve atpressures over 1/2 psig.The manifold pressure is controlled by a regulatorbuilt into the gas control, and should be checkedat the pressure test point.Note: To properly check gas pressure, bothinlet and manifold pressures shouldbe checked using the valve pressureports on the valve.1) Make sure the valve is in the "OFF" position.2) Loosen the "IN" and/or "OUT" pressuretap(s), turning counterclockwise with a1/8" wide flat screwdriver.3) Attach manometer to "IN" and/or "OUT"pressure tap(s) using a 5/16" ID hose.4) Light the pilot and turn the valve to "ON"position.5) The pressure check should be carried outwith the unit burning and the setting shouldbe within the limits specified on the safetylabel.6) When finished reading manometer, turnoff the gas valve, disconnect the hose andtighten the screw (clockwise) with a 1/8" flatscrewdriver. Note: Screw should be snug,but do not over tighten.SIT 829 VALVE DESCRIPTION1) Gas on/off knob2) Electronically Operated Hi/Lo3) Pilot Adjustment4) Thermocouple Connection - option5) Outlet Pressure Tap6) Inlet Pressure Tap7) Pilot Outlet8) Main Gas Outlet9) Alternative TC Connection Point