Regency ® PG36D Gas Log Fireplace6INSTALLATIONMin. 6"(152mm)Min. 8"(203mm)30-1/2" (775mm)Top of UnitMin. 32" (1016mm)to Ceiling"Clearances for Bay or Flush FrontClearances for Barcelona FrontNOTE: The minimum floor clearance mustbe maintained from the top surface of thecarpeting, tile, etc.Minimum Clearance from Top of Unit to:Mantel* Minimum 7" (177mm)Ceiling from top of unit. 32" (1016mm)Side Wall ClearanceBay or Flush Front 6" (152mm)Barcelona Trim 8" (203mm)Horizontal Flue ClearancesTop 2" (51mm)Side 1-1/2" (38mm)Bottom 1-1/2" (38mm)Vertical Flue Clearances 1-1/4" (32mm)Alcove Clearances**:Max. Depth 36" (914mm)Min. Width 48" 1219mm)Min. Height 72" 1829mm)* see mantle clearance instructions(Refer to section "Combustible Mantels" &"Mantel Leg Clearances."**Approved for one sidewall installationonly when using Barcelona FrontCLEARANCESThe clearances listed below are Minimumdistances unless otherwise stated:A major cause of chimney related fires isfailure to maintain required clearances (airspace) to combustible materials. It is of thegreatest importance that this fireplace andflue system be installed only in accordancewith these instructions.Clearance to Combustibles from:Back 0" (0mm)Side 0" (0mm)Floor 0" (0mm)Diagram 1LOCATING YOURGAS FIREPLACE1) When selecting a location for your stove,ensure that the clearances outlined on thispage are met.2) P r o v i d e a d e q u a t e c l e a r a n c e s f o rservicing.3) The appliance must be installed on a flat,solid, continuous surface (e.g. wood, metal,concrete). This may be the floor, or raised upon a platform to enhance its visual impact.If the appliance is going to be installedon carpeting, combustible linoleum tile orother combustible material other than woodflooring, the appliance must be installed ona metal or wood panel extending the fullwidth and depth of the appliance.4) The PG36D Co Axial Flue Gas Fireplacecan be installed in a recessed position orframed out into the room as in A, B, C, D.SeeDiagram 1.MANUFACTUREDMOBILE HOMEADDITIONALREQUIREMENTS1) Ensure that structural members are not cutor weakened during installation.2) Ensure proper grounding using the #8 groundlug provided. See section "Wiring."A) Flat on WallB) Flat on Wall CornerC) Recessed into Wall/AlcoveD) Corner5) This appliance is Listed for bedroominstallations when used with a Listed MillivoltThermostat. Some areas may have furtherrequirements, check local codes beforeinstallation.6) The PG36D Co Axial Flue Gas Fireplaceis approved for alcove installations, whichmeet the clearances listed on this page.7) We recommend that you plan your installationon paper using exact measurements forclearances and floor protection beforeactually installing this appliance. Have anauthorized inspector, dealer, or installerreview your plans before installation.Note: For flue terminations see section" E x t e r i o r F l u e Te r m i n a t i o nLocations."WARNINGFire hazard is anextreme riskif these clearancesare not adhered to.For more Barcelona Framing and InstallationNotes, see section "Framing and Finishing."BARCELONA FRAMING NOTE: If theBarcelona Front is to be installed, the frontface of the fireplace must be made of non-combustible material. See Diagram 1.SteelStudSteelStudM in.12"(305m m )M in.6"(153m m )M in.6"(153m m )37-1/4"(946m m )30-1/2"(775m m )36-1/4"(921m m )FrontFram ing D im ensions usingthe B arcelona O ptionN on-com bustibleM aterialDiagram 1