Regency Plateau® PTO30-1 Outdoor Gas Fireplacee | 1313|installationGAS PIPE PRESSURETESTINGThe appliance must be isolated from the gas sup-ply piping system by closing its individual manualshut-off valve during any pressure testing of thegas supply piping system at test pressures equalto or less than 1/2 psig. (3.45 kPa). Disconnectpiping from valve at pressures over 1/2 psig.The manifold pressure is controlled by a regulatorbuilt into the gas control, and should be checkedat the pressure test point.Note: To properly check gas pressure, bothinlet and manifold pressures should bechecked using the valve pressure portson the valve.1. Make sure the valve is in the "OFF" position.2. Loosen the "IN" and/or "OUT" pressure tap(s),turning counterclockwise with a1/8" wide flat screwdriver.3. Attach manometer to "IN" and/or "OUT" pressuretap(s) using a 5/16" ID hose.4. Light the pilot and turn the valve to "ON" position.5. The pressure check should be carried out withthe unit burning and the setting should be withinthe limits specified on the safety label.6. When finished reading manometer, turn off thegas valve, disconnect the hose and tighten thescrew (clockwise) with a 1/8" flat screwdriver.Note: Screw should be snug, but do not overtighten.AERATION ADJUSTMENTThe burner aeration is factory set but may needadjusting due to either the local gas supply oraltitude. Open the air shutter for a blue flame orclose for a more yellow flame.Minimum Air Shutter Opening:Fully Closed NG1/2" LPNote: Any damage due to carboning resultingfrom improperly setting the aerationcontrols is NOT covered under warranty.HIGH ELEVATIONThis unit is approved for altitude 0 to 4500 ft. (CAN/CGA 2.17-M91).GAS LINEINSTALLATIONSince some municipalities have additional localcodes it is always best to consult with your localauthorities and the CAN/CGA B149 installationcode.For USA installations follow local codes and/or thecurrent National Fuel Gas Code, ANSI Z223.1.When using copper or flex connectors use onlyapproved fittings. Always provide a union so thatgas lines can be easily disconnected for servicing.Flare nuts for copper lines and flex connectors areusually considered to meet this requirement.NOTE: A shutoff / dante valve should be sup-plied in or near the unit (or as per local codes)for ease of servicing this appliance.IMPORTANT: Always check for gas leaks witha soap and water solution or gas leak detector.Do not use open flame for leak testing.PTO30-NG1 SYSTEM DATAMax. Supply Pressure 14" WC (3.49 kpa)Min. Supply Pressure 5" WC (1.25 kpa)Manifold Pressure 3.5" WC (0.87 kpa)Manifold Pressure -Low 1.6" WC (0.40 kpa)Orifice Size #25 DMSMinimum Input 30,000 Btu/h(8.79 kW)Maximum Input 50,000 Btu/h(14.65 kW) 3PTO30-LP1 SYSTEM DATAMax. Supply Pressure 14" WC (3.49 kpa)Min. Supply Pressure 11" WC (2.73 kpa)Manifold Pressure 10" WC (2.49 kpa)Manifold Pressure-Low 6.4" WC (1.59 kpa)Orifice Size #45 DMSMinimum Input 38,000 Btu/h(11.13 kW)Maximum Input 49,000 Btu/h(14.36 kW)Note: If you have an incorrect flame pattern,contact your Regency ® dealer for furtherinstructions.Incorrect flame pattern will have small, probablyyellow flames, not coming into proper contactwith the rear burner or flame sensor.BurnerFlame SensorPilot IgnitorPILOT ADJUSTMENTPeriodically check the pilot flames. Correct flamepattern has two strong blue flames: 1 flowingaround the flame sensor and 1 flowing acrossthe burner (it does not have to be touching theburner).886 S.I.T. VALVEDESCRIPTION1) Manual high/low adjustment2) Pilot adjustment3) Outlet Pressure Tap4) Inlet Pressure Tap5) Pilot Outlet6) Main Gas Outlet7) Main Gas Inlet13241324567NOTE:The PTO60 has a combined min. input of 60,000Btu - NG/ 76,000 Btu - LP and max. input of100,000 Btu - NG / 98,000 Btu - LP.Care should be taken when sizing the gas pipedue to the extremely high Btu of this unit.