16AWiring work(Cont.)X Select the power cable in accordance with relevant local and national regulations.X Wire size must comply with local and national code.X For the power cable, use the grade of H07RN-F or H05RN-F materials.X You should connect the power cable into the power cable terminal and fasten it with a clamp.X The unbalanced power must be maintained within 10% of supply rating among whole indoorunits.X If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalancedpower is exceeded over 10% of supply rating, the indoor unit is protected, stopped and theerror mode indicates.X To protect the product from water and possible shock, you should keep the power cable andthe connection cord of the indoor and outdoor units in the iron pipe.X Connect the power cable to the auxiliary circuit breaker.An all pole disconnection from the power supply must be incorporated in the fixedwiring(≥3mm).X You must keep the cable in a protection tube.X Keep distances of 50mm or more between power cable and communication cable.X Maximum length of power cables are decided within 10% of power drop. If it exceeds, youmust consider another power supplying method.X The circuit breaker(ELCB or MCCB+ELB) should be considered more capacity if many indoorunits are connected from one breaker.X Use round pressure terminal for connections to the power terminal block.X For wiring, use the designated power cable and connect it firmly, then secure to prevent out-side pressure being exerted on the terminal board.X Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a smallhead will strip the head and make proper tightening impossible.X Over-tightening the terminal screws may break them.X See the table below for tightening torque for the terminal screws.Tightening torqueNtm kgftcmM3.5 0.8~1.2 8.0~12.0M4 1.2~1.8 12.0~18.0CAUTION