25Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXXOption SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Explanation PAGE MODEUse of Auto ChangeOver for HR only inAuto mode(When setting SEG3)Standard heatingtemp. Offset(When setting SEG3)Standard coolingtemp. Offset(When setting SEG3)Standard for modechangeHeating CoolingRemoteControllerDisplayIndicationand DetailsIndication Details Indication Details Indication Details Indication Details Indication Details Indication Details0 5Followproductoption0 0 0 0 0 11Use AutoChangeOver forHR only1 0.5 1 0.5 1 1.52 1 2 1 2 23 1.5 3 1.5 3 2.54 2 4 2 4 35 2.5 5 2.5 5 3.56 3 6 3 6 47 3.5 7 3.5 7 4.5Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12Explanation PAGE(When setting SEG3)Standard for modechanging CoolingHeating mode(When setting SEG3)Time required formode changeCompensation optionfor Long pipe or heightdiffference betweenindoor unitsRemoteControllerDisplayIndicationand DetailsIndication Details Indication Details Indication Details Indication Details10 1 0 5 min. 0 Use defaultvalue1 1.5 1 7 min.11) Heightdifference1)is more than30m or2) Distance2)is longerthan 110m2 2 2 9 min.3 2.5 3 11 min.4 3 4 13 min.21) Heightdifference1) is15~30m or2) Distance2)is 50~110m5 3.5 5 15 min.6 4 6 20 min.7 4.5 7 30 min.Q 05 series installation option(Detailed)