parameters vacon • 4124-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com88.3 Start/stop setup (Control panel: Menu PAR -> P2)8.4 Frequency references (Control panel: Menu PAR -> P3)NOTE! These parameters are shown, when P13.1 = 0.Code Parameter Min Max Unit Default ID NoteP2.1 Control place 1 3 1 1251 = I/O terminal2 = Keypad3 = FieldbusP2.2 Start function 0 1 0 505 0 = Ramp1 = Flying startP2.3 Stop function 0 1 0 506 0 = Coasting1 = RampP2.4 Start/Stoplogic 0 3 0 300DI1 DI20 Start Fwd Start reverse1 Start Reverse2 Start Pulse Stop Pulse3 Start Fwd Start RvREAF REAFTable 8.3: Start/stop setupCode Parameter Min Max Unit Default ID NoteP3.1 Min frequency 0,00 P3.2 Hz 0,00 101P3.2 Max frequency P3.1 320 Hz 50,00 102P3.3 I/O reference 0 4 3 1170 = Preset Speeds (0-7)1 = Keypad Reference2 = Fieldbus Reference3 = AI1 (API FULL &LIMITED)4 = AI2 (API FULL)P3.4 Preset speed 0 0,00 P3.2 Hz 5,00 124 Activated by digital inputsP3.5 Preset speed 1 0,00 P3.2 Hz 10,00 105 Activated by digital inputsP3.6 Preset speed 2 0,00 P3.2 Hz 15,00 106 Activated by digital inputsP3.7 Preset speed 3 0,00 P3.2 Hz 20,00 126 Activated by digital inputsP3.8 Preset speed 4 0,00 P3.2 Hz 25,00 127 Activated by digital inputsP3.9 Preset speed 5 0,00 P3.2 Hz 30,00 128 Activated by digital inputsP3.10 Preset speed 6 0,00 P3.2 Hz 40,00 129 Activated by digital inputsP3.11 Preset speed 7 0,00 P3.2 Hz 50,00 130 Activated by digital inputsTable 8.4: Frequency references