72 • vacon parameters88.2 Motor settings (Control panel: Menu PAR -> P1)Code Parameter Min Max Unit Default ID NoteMotor nominalvoltage 180 690 V Varies 110 Check rating plate on themotorMotor nominal fre-quency 30,00 320,00 Hz 50,00 /60,00 111 Check rating plate on themotorMotor nominalspeed 30 20000 rpm 1440 /1720 112 Default applies for a 4-polemotor.Motor nominalcurrent0,2 xINunit2,0 xI Nunit A I Nunit 113 Check rating plate on themotorMotor cos(Power Factor) 0,30 1,00 0,85 120 Check rating plate on themotorMotor type 0 1 0 650 0 = Induction1 = Permanent magnetCurrent limit 0,2 xINunit2,0 xI Nunit A 1,5 xI Nunit 107 Maximum motor currentMotor controlmode 0 1 0 600 0 = Frequency control1 = Open loop speed controlU / f ratio 0 2 0 1080 = Linear1 = Square2 = ProgrammableField weakeningpoint 8,00 320,00 Hz 50,00 /60,00 602 Field weakening point fre-quencyField weakeningpoint voltage 10,00 200,00 % 100,00 603 Voltage at field weakeningpoint as % of UnmotU / f mid pointfrequency 0,00 P1.10 Hz 50,00 /60,00 604 Mid point frequency forprogrammable U / fU / f mid pointvoltage 0,00 P1.11 % 100,00 605Mid point voltage for pro-grammable U / f as % ofU nmotZero freq voltage 0,00 40,00 % Varies 606 Voltage at 0 Hz as % of UnmotTorque Boost 0 1 0 109 0 = Disabled1 = EnabledSwitchingfrequency 1,5 16,0 kHz 4,0 / 2,0 601PWM frequency. If valuesare higher than default,reduce the current capacityTable 8.2: Motor settingsP1.1P1.2P1.3iiiiiiiiiiP1.4P1.5 P1.6P1.7P1.8P1.9P1.10P1.11P1.12P1.13P1.14P1.15P1.16Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com