parameters vacon • 9188.17 Motor Pre-heat (Control panel: Menu PAR -> P16)8.18 Easy usage menu (Control panel: Menu PAR -> P17)Code Parameter Min Max Unit Default ID NoteP16.1 Motor Pre-heatFunction 0 2 0 12250 = Not used1 = Always in stop state2 = Controlled by digitalinputP16.2 Motor Pre-heatCurrent 0 0,5 xINunit A 0 1227DC current for Pre-heat-ing of motor and drive instop state. Active in stopstate or by digital inputwhile in stop state.Table 8.17: Motor Pre-heatCode Parameter Min Max Unit Default ID NoteApplication Type 0 3 0 5400 = Basic1 = Pump2 = Fan drive3 = High TorqueNOTE! Visible only whenStartup wizard is active.P17.2 Parameterconceal 0 1 1 1150 = All parameters visible1 = Only quick setupparameter group visibleP17.3 Temperatureunit 0 1 0 11970 = Celsius1 = KelvinsNOTE! Hidden until anOPTBH board is con-nected.Table 8.18: Easy usage menu parametersi P17.1Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com