Installation vacon • 63Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/55.2.2 LCL filterEnough free space must be left around the LCL filter to ensure sufficient air circulation and cooling.You will find the required dimensions for free space in the Table 29. You will find the required coolingair, minimum air holes and heat dissipation in the Table 30.When planning the cooling for the space, take into consideration that the LCL filter heat loss isapprox. 1% of the nominal capacity. Air flow, see Figure 34 and Figure 35.Figure 33. Installation spaceTable 29. Mounting space dimensionsType Dimensions [mm]A B B 2 CLCL0261 5LCL0170 6 350 0 20 0LCL0460 5LCL0325 6 350 0 20 0LCL1300 5LCL1030 6 350 0 20 0A = free space above the LCL filterB = distance between LCL filter and cabinet wallB BB2B2AACC11217.emf