9vacon • 76 CONTROL KEYPADTel. +358 (0) 201 2121 • Fax +358 (0)201 212 205Figure 46. Parameter value change procedure9.3.3 Keypad control menu (M3)In theKeypad Controls Menu, you can choose the control place, edit the frequency reference andchange the direction of the motor. Enter the submenu level with theMenu button right.9.3.3.1 Selection of control placeThere are three different places (sources) which the frequency converter can be controlled from.For each control place, a different symbol will appear on the alphanumeric display:Change the control place by entering the edit mode with theMenu button right. The options can thenbe browsed through with theBrowser buttons. Select the desired control place with theEnterbutton. See the diagram on the next page. See also 9.3.3 above.Table 25. Keypad control parameters, M3Code Parameter Min Max Unit Default Cust ID NoteP3.1 Control place 1 3 1 1251 = I/O terminal2 = Keypad3 = FieldbusR3.2 Keypad reference Par. 2.1.1 Par.2.1.2 HzP3.3 Direction (on keypad) 0 1 0 123 0 = Forward1 = ReverseR3.4 Stop button 0 1 1 114 0 = Limited function of Stop button1 = Stop button always enabledControl place symbolI/O terminalsKeypad (panel)FieldbusG1G8READYKeypadP1P18READYKeypad13.95 HzREADYKeypadG1G8KeypadREADYKeypad13.95 Hz enterREADYKeypad14.45 HzParameters Basic parameters Min FrequencyInput signalsMin Frequency Min Frequency11529_ukI/O termKeypadBus/Comm