Supplied By www.heating spares.co Tel. 0161 620 6677Gas supply adjustments (Com. Part II) 7Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 337.8 Fit combustion chamber coverCarefully re-fit the combustion chamber cover to theboiler ensuring it is correctly sealed. Secure cover withretaining clamps.7.9 Fit boiler casing• Carefully push case (1) onto the boiler such that thelocating points either side at the top of the boilerengage. Push the casing onto the securing clips at thebottom of the boiler.• Close control panel (2).• Secure control panel by turning both securingfasteners (3) clockwise by 90°.• Fit and close front door (4).• Fit lower cover plate (5).Fig. 5.21: Fit boiler casingVRC-VC142I090°90°358 Functional Checks8.1 Functional checksProcedureOnce the unit has been installed and the gas supply hasbeen checked, operate the system to ensure that it isworking correctly.• Operate the system, following the operatinginstructions supplied with the boiler.• Check the system for water leaks and escaping gas.• Check that the flue has been correctly installed,according to the fitting instructions supplied with theflue assembly.• Check the burner for correct ignition and flamepicture.• ttuurrbbooMMAAXX pplluuss oonnllyy:: Check the hot water systemfor correct operation.• Check the heating system for correct operation.Fig. 8.1 Test for correct functioning8.2 Functional check of operation(turboMAX plus only)This boiler is fitted with indicator lights to display theoperating status of the boiler. The status of theindicators in normal operation will be as follows.Boiler in stand by mode• Red lock out indicator (1) OFF.• Yellow flame indicator (2) OFF.• Green warmstart indicator (3):- ON – Warmstart ON- OFF – Warmstart OFFHot water operation• Fully open hot water tap.If boiler is operating correctly, the status of theindicators will be as follows:• Red lock out indicator (1) OFF.I0