ecoTEC exclusive installation and maintenance instructions / 0020017768_04307.2 Overview of the settable installation parametersThe following parameters can be set to match theappliance to the heating system and to suit thecustomers requirements:Display Meaning Adjustable parameters DefaultsettingAppliance-specificsettingd.0 Heating partial load ecoTEC exclusive 832ecoTEC exclusive 83827 kW30 kW22 kW27 kWd.1 Pump overrun time for heating operation(starts after completion of heat demand)2 - 60 min 5 mind.2 Max. blocking time heating at 20°C feedtemperature2 - 60 min 20 mind.14 Pump speed target value Target value internal pump in % - possible set-tings: Auto, 53, 60, 70, 85, 100 %Autod.17 Heating flow/return regulation changeover 0 = flow, 1 = return 0d.18 Pump mode (return flow) 0 = return, 1 = nonstop, 2 = winter 0d.26 Changeover option relay to electronic 1 = circulation pump2 = Ext. pump (default)3 = storage charging pump4 = vapour extraction hood5 = external throttle6 = ext. fault signal (without maintenance dis-play)2d.71 Target value max. heating flow temperature 40 to 85 °C 75 °Cd.84 Maintenance indicator: Number of hoursuntil the next maintenance0 to 3000h and „-“(300 corresponds to 3000 h, „-“ = deactivated)-Table 7.1 Adjustable parametersh Note!You can enter your settings in the end columnafter setting the appliance-specific parameters.h Note!The diagnosis points d.17, d.71 and d.84 are lo-cated in the 2nd. diagnosis level, see Chapter9.1.27.2.1 Setting the heating partial loadThe units are set in the factory to a possible heat loadbut not yet to the maximum value. Under diagnosispoint "d.0" you can set a value which corresponds tothe required output in the heating system in kW.7.2.2 Setting the pump overrun timeThe pump overrun time for the heating operation is set inthe factory to a value of 5 minutes. It can be set underdiagnosis point "1" within the range two minutes to60 minutes. Under diagnosis point "d.18" you can set theoverrun behaviour of the pump to a different mode.Overrun: After completion of the heat demand the heatingpump continues to run for the time set under "d.1".Continuous: The internal heating pump is switchedon when the rotary knob for setting the heating feedtemperature is not in the left-hand stop position and theheat demand is released by an external controller.Winter: The internal heating pump is switched on whenthe rotary knob for setting the heating feed temperatureis not in the left-hand stop position.7.2.3 Setting the maximum flow temperatureThe maximum feed temperature for the heating is set inthe factory to 75 °C. Under diagnosis point "d.71" it canbe set to between 40 und 85 °C.7.2.4 Setting the return temperature controlWhen connecting underfloor heating or wall heating tothe appliance which does not have its own temperatureregulation, the temperature regulation mode can bechanged from feed temperature regulation (factory set-ting) to return temperature regulation under diagnosispoint "d.17".7 Adapting the appliance to the heating system