Control lamp for indication of the switching condition.l green = switch closedl red = switch openl red (flashing) = failureThe adjustment of the switching point is only possible ininstalled condition.The specifications in parenthesis refer to the above illustration.Vertically mounted probes1 Set mode switch (3) to mode max.2 Set meas. range selection switch (2) to range 1.3 Fill the vessel up to the requested level.4 Turn the potentiometer (1) to 10; the control lamp (6) lightsgreen.5 Turn the potentiometer (1) very slowly anticlockwise untilthe control lamp (6) lights red. If the control lamp does notlight red, then you have to set the meas. range selectionswitch (2) to the next higher stage and repeat the settingwith the potentiometer (1) until the control lamp lights red.The measuring system is now ready for operation.1 Set mode switch (3) to mode min.2 Set meas. range selection switch (2) to position 1.3 Lower the level to the requested min. level.4 Turn the potentiometer (1) to 0; the control lamp (6) lightsgreen.5 Turn the potentiometer (1) very slowly clockwise until thecontrol lamp (6) lights red. If the control lamp does not lightred, set the meas. range selection switch (2) to the nexthigher stage and repeat the setting with the potentiometer(1) until the control lamp lights red.The measuring system is now ready for operation.6.3 Function chartThe following chart provides an overview of the switchingconditions depending on the adjusted mode and level.Signal lamp (6)Switching point adjustmentMode max. (max. de-tection)Mode min. (min. detection)VEGACAP 65 - with contactless electronic switch 21Set up30017-EN-060223