2.6 Safety information for Ex areasPlease note the Ex-specific safety information for installationand operation in Ex areas. These safety instructions are part ofthe operating instructions manual and come with the Ex-approved instruments.2.7 Manufacturer declarationIn conformity with DIN EN 60079-14/2004, para. 5.2.3, pointc1, the capacitive probe VEGACAP 65 is suitable for use inzone 2.The operator must use the instrument correctly and follow thespecifications of the following documents:l this operating instructions manuall this manufacturer declaration (24643)l the corresponding installation regulationsMax. increase of the surface temperature during operation:40 K (individual components in the instrument)With an ambient temperature of +70°C (+158°F) on thehousing and a process temperature of +70°C (+158°F), themax. ambient temperature during operation is +110°C(+230°F).Measures to maintain the explosion protection during oper-ation:l Operate the instrument in the range of the specifiedelectrical limit values. Permissible supply voltage: see"Technical data"l Mount and operate the instrument in such a way that noignition danger is expected by electrostatic charges. Theprocess fitting, the plastic-coated/covered probe part or thehousing are made of electrically non-conductive plastic(depending on the version).l Make sure that the seal is mounted correctly betweenlower part of the housing and cover. Screw the cover ontightly.l Make sure that there is no explosive atmosphere, if youwant to operate the instrument with open coverl Make sure that the cable gland is tight and strain-relieved.The outer diameter of the connection cable must beadapted to the cable gland. Tighten the pressure screw ofthe cable gland carefully.l Cover unused openings for cable glands tightly6 VEGACAP 65 - with contactless electronic switchFor your safety30017-EN-060223